Model meaning
Product overview
This series load switch is researched and developed by our company in 2003 for XGN14-12SF6 ring main unit, with high economical efficiency, safety and reliability, is featured with simple structure, flexible operation, reliable interlocking, convenient installation. It meets the standards IEC60694, GB3804, GB16926, etc.
Cable incoming/outgoing schemeBoth the main circuit and ground circuit of FLN48-12D are sealed in the insulation shell that is made of epoxy resin by means of APG casting process, with good insulation performance, anti-pollution, etc. The insulation shell is made up of upper and lower two insulating covers with SF6 gas inside whose relative pressure is 0.4bar. The lower insulating cover has explosion precautions to guarantee personal safety, the overpressure SF6 will break through the blow-out disc in lower insulating cover and be led to the back of the box in case of accident conditions.
FLN48-12D load switch adopts arc chute structure that enjoys quick and reliable arc extinguishing. FLN48-12D load switch can be divided into two types: FLN48-12D (K type single-spring operating mechanism) and FLRN48-12D (A type single-spring operating mechanism). The latter can be combined into load switch + fuse combination unit with control and protection functions
Service conditions
● Ambient temperature
Max temperature: +40℃
Mix temperature: -40℃
● Humidity: max average relative humidity
Daily mean: ≤95%
Monthly mean: ≤90%
● Seismic capacity: Ms8
● Altitude: ≤2000m
● The ambient air should be free of obvious pollution of corrosive gas or combustible gas or water vapor.
The installation site should be free of regular intensive vibration.
● Annual leakage rate: ≤0.1%
● Special conditions: please specify clearly if the load switch is intended for altitude 2000m above, so that the manufacturer can regulate the design scheme for you. (So far we have manufactured special load switch that run safely at altitude about 5000m).
Technical parameters
Unit FLN36-12D/T630-20 type load switch FLRN36-12D/100-50 type load switch-fuse combination unit
Rated voltage KV 12 12
Rated frequency Hz 50 50
Rated current A 630 100
1min power frequency withstand voltage, phase-to-ground and phase-to-phase KV 42/48 42/48
Lightning impulse withstand voltage (peak) phase-to-ground and phase-to-phase/isolating distance KV 75/8575/85
Rated power frequency withstand voltage under zero gauge pressure for 5min KV 24 24
Rated short-time withstand current 3s/2s, load switch / earthing switch KA 20/20 20/20
Rated peak withstand current (peak), load switch / earthing switch KA 50/50 50/50
Rated short-circuit making current, load switch / earthing switch KA 50/50 125/50
Rated closed loop breaking current A 630
Rated active load breaking current A 630
Rated cable charging breaking current A 10 10
Rated short-circuit breaking current KA 50*
Rated transfer current A 1700
Type of fuse XRNT-12KV/100A*
Output energy of fuse striker J 1±0.5
Mechanical life, load switch / earthing switch Times 5000/2000 3000/2000
Air insulation distance between electrified bodies and to ground mm ≥125 ≥125
SF6 gas pressure (relative pressure at 20℃) bar 0.4 0.4
Opening and closing synchronism ms ≤2 ≤2
Resistance of main circuit μΦ ≤65 ≤65